automatic ignition
Up to 900 kW nominal power and at a maximum fuel moisture of M 35, electric industrial hot air blowers are available for igniting the fuel in the firing pan or on the moving grate.
The compact firing system for dry chips, moist wood chips as well as residual wood.
1. stoking with stoker
2. fire trough with large grate ribs and primary air supply
3. burnout grate
4. combustion chamber
5. secondary air inlet
6. radiation vault
7. 3 draughtheat exchanger
8. controlled boiler bypass (optional)
9. multicyclone with automatic discharge of fly ash
10. boiler door with pneumatic boiler tube cleaning system
11. furnace door with safety lock
12. automatic discharge of grate ash into ash garbage can or container
13. ash garbage can or container
14. boiler cladding for reduced radiation loss and noise emissions
15. air intake openings
16. pressure relief damper
17. automatic pressure surge cleaning boiler bypass (optional)
18. cleaning opening on both sides for multicyclone
13. ash garbage can or container
14. boiler cladding for reduced radiation loss and noise emissions
17. automatic pressure surge cleaning boiler bypass (optional)
18. cleaning opening on both sides for multicyclone
19. flue gas recovery (optional)
20. fly ash garbage can
Boiler size | Unit | 180 / 200 | 300 / 360 | 450 / 550 | 700 / 900 |
---|---|---|---|---|---|
Rated power at M45 | kW | 54 - 240 | 90 - 360 | 135 - 550 | 210 - 900 |
Mass (L x W x H) | mm | 3275 x 1150 x 2290 | 3495 x 1250 x 2340 | 4005 x 1440 x 2540 | 4625 x 1600 x 3090 |
Water content boiler | l | 645 | 855 | 1315 | 2355 |
Weight Tota with water | kg | 5410 | 6455 | 8815 | 10640 |
You can find more information about our discharge systems here >>.
Schmid AG wood-burning furnaces have intuitive operation - the Personal Touch visio control system. It guarantees optimal combustion conditions with high efficiencies. In addition to a modern design and high user-friendliness, the web technology HMTL5, the worldwide standard for modern web browsers, is in use.
The use of this technology results in versatile possibilities of how the firing systems can be operated. Four independent connections can be made simultaneously to the plant for operation via a smartphone, tablet or the built-in touch panel.
You can find more information about the new PersonalTouch visio operation here >>.
Are you replacing a fossil gas or oil heating system with a renewable heating system? Benefit from attractive subsidies.
Gewerbe | Holzhackschnitzel | Holzspäne | Holzverarbeitende Betriebe | Industrie | Nah- und Fernwärme | Restholz | Rinde | Unterschubrostfeuerung UTSK viso | UTSK visio
Wood chips | Wood processing companies | Local and district heating | UTSK visio
Benefit from our many years of experience and let our specialists advise you individually, without obligation and free of charge.
The underfeed firing system UTSK visio is suitable for dry chips, moist wood chips, as well as residual wood wood chips. This combustion plant is mainly used as a variant for new plants and as a replacement for existing oil or gas firing systems.
In the UTSK visio underfeed firing system, the material is fed from below into a combustion retort made of high-alloy cast iron. The complete combustion chamber is lined with refractory material and ensures a high firing temperature even with moist material. A radiant ceiling is installed above the combustion chamber, which varies depending on the material. The primary air is fed through the cast rods in the combustion retort, where it produces a quiet gasification of the fuel material. The secondary air supplied in the combustion chamber ensures optimum burnout and thus low emission levels. Ash removal takes place via a burnout grate. An ash screw is arranged under the burnout grate, with which the ash is conveyed directly into an ash bucket or into a container. The combustion unit is completely surrounded by the primary and secondary air and, together with the effective insulation, ensures minimum radiation.
A well-dimensioned 3-pass flue tube boiler is installed above the furnace. The multicyclone is installed directly behind the heat exchanger and can be optimally supplied with air.